should act to bring the voltage down to a safe level before equipment damage occurs.
However, in the event of a regulator failure, the BE1-24 protects equipment from
damage.
Load tap changing (LTC) transformers and line voltage regulators may be subjected to
excessive volts/hertz during abnormal system frequency conditions.
This is the inevitable consequence of their constant voltage control function. Failure of
the LTC controller may result in a runaway condition producing dangerously high
voltages. The BE1-24 provides close protection for such equipment while allowing a
wide range of voltage control operations.
Figure 1-1 illustrates the advantage of applying the inverse square timing characteristic
rather than the two step protection scheme. This provides closer coordination and
prevents unnecessary tripping of the protected equipment.
In this example, two steps of definite time delay overexcitation protection are applied
to provide protection that approximates the transformer damage curve.
One step is set for 110 percent and 60 seconds. The second step is set for 118 percent
and 6 seconds. However, by using the inverse square characteristic, the damage curve
can be even more closely approximated. The resulting protection is more closely
coordinated with adequate margin. Note that the cross hatched area reveals the
overprotected area that results from use of a two step scheme.
When a transformer and generator are to be protected by a single volts-per-hertz
overexcitation relay, the overexcitation curves for both pieces of equipment must be
considered. Figure 1-2 illustrates a situation where these two units have different
characteristics and yet can both be protected by the BE1-24. Utilizing the alarm function
(with its definite time delay), and in combination with the inverse square characteristic,
the transformer generator combination may be protected with a single BE1-24 Volts-Per
-Hertz Overexcitation Relay. If necessary, the instantaneous element can be set to a
percentage (105%) of the rated excitation to provide an early warning alarm.
This alarm can enable the operator controlling the excitation to recover and prevent
tripping.