DESCRIPTION
The Horner APG Thermocouple Input Modules allow thermocouple temperature sensors to be directly
connected to the PLC without external signal processing (transducers, transmitters, etc.). All analog and
digital processing of the thermocouple signal is performed on the module. These modules have a
resolution of 0.5°C, and temperature values may be reported to the PLC %AI I/O table in 0.5°C or 0.5°F
increments. There are four standard resolution models available, with four input channels
(HE693THM409/HE693THM449), and with eight input channels (HE693THM809/HE693THM889). All
models feature open circuit detection, where the temperature value written to the %AI register goes to its
maximum value upon an open circuit condition. Two models (HE693THM449 and HE693THM889) also
feature %I alarm bits which energize on an open circuit condition. The first four %I bits are used for the
HE693THM449 and the first eight %I bits are used for the HE693THM889.
General
In order to meet CISPR (EN 55011) Group 1. Class A Radiated Emissions levels, all components in the
PLC system require the following:
• All components must be mounted in a metal enclosure or the equivalent. The wiring must be
routed in metal conduit or the equivalent. All surfaces of the enclosure must be adequately
grounded to adjacent surfaces to provide electrical conductivity.
• The metal conduit (flexible conduit is acceptable) for all wiring external to the cabinet must be
mounted to the enclosure using standard procedures and hardware to ensure electrical
conductivity between the enclosure and the conduit.
• An external EMI filter must be wired to the AC Main for the PLC. Sprague Electric Part
Number 259A9098P3 (available from GE Fanuc), or any other EMI filter which provides
equivalent performance, may be used.
• An external ground wire (16 AWG (1.32 mm2), 6" (15.24 cm) maximum length) must be wired
from the Series 90-30 power supply safety ground wire terminal to the metal enclosure.
• On AC Main Ports connected to PLCs, MOVs shall be connected Line to Line and Line to Ground.
• All cables and Analog signals must use shielded cable with a minimum of overall foil.